range of product |
EasyPact
| |
product or component type |
Circuit breaker
| |
device short name |
Easypact EZC400H
| |
circuit breaker name |
Easypact EZC400H
| |
device application |
Distribution
| |
poles description |
3P
| |
protected poles description |
3t
| |
network type |
DC
AC | |
network frequency |
50/60 Hz
| |
[In] rated current |
400 A ( 40 °C )
| |
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
| |
[Uimp] rated impulse withstand voltage |
8 kV conforming to IEC 60947-2
| |
[Ue] rated operational voltage |
250 V DC conforming to IEC 60947-2
440 V AC 50/60 Hz conforming to IEC 60947-2 | |
breaking capacity code |
H
| |
breaking capacity |
HIC 35 kA at 277/480 V AC 50/60 Hz conforming to NEMA AB1
HIC 85 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 Icu 100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 Icu 20 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 Icu 40 kA at 250 V DC 2P conforming to IEC 60947-2 Icu 50 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 Icu 50 kA at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Ics] rated service breaking capacity |
Ics 10 kA 550 V AC 50/60 Hz conforming to IEC 60947-2
Ics 20 kA 250 V DC conforming to IEC 60947-2 Ics 25 kA 380 V AC 50/60 Hz conforming to IEC 60947-2 Ics 25 kA 400/415 V AC 50/60 Hz conforming to IEC 60947-2 Ics 25 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 Ics 50 kA 220...240 V AC 50/60 Hz conforming to IEC 60947-2 Ics 17.5 kA 277/480 V AC 50/60 Hz conforming to NEMA AB1 Ics 42.5 kA 240 V AC 50/60 Hz conforming to NEMA AB1 | |
suitability for isolation |
Yes conforming to IEC 60947-2
| |
utilisation category |
Category A
| |
trip unit name |
TM-D
| |
trip unit technology |
Thermal-magnetic
| |
trip unit rating |
350 A ( 50 °C )
| |
protection type |
Overload protection
Short-circuit protection | |
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
| |
mounting mode |
Fixed
| |
mounting support |
Backplate
| |
upside connection |
Front
| |
downside connection |
Front
| |
mechanical durability |
4000 cycles
| |
electrical durability |
Category A : 1000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
| |
connection pitch |
44 mm
| |
local signalling |
Positive contact indication
| |
neutral protection setting |
Without protection
| |
earth-leakage protection |
Without
| |
height |
255 mm
| |
width |
185 mm
| |
depth |
140 mm
|
standards |
GB 14048.2
JIS C8201-2-2 EN 60947-1 IEC 60947-1 NEMA AB1 IEC 60947-2 EN 60947-2 CSA C22.2 No 14 UL 508 | |
IP degree of protection |
IP20 conforming to IEC 60529
| |
IK degree of protection |
IK07 conforming to EN 50102
| |
ambient air temperature for operation |
-25...70 °C
| |
ambient air temperature for storage |
-35...85 °C
|
Warranty period |
18 months
|
circuit breaker Easypact EZC400H - TMD - 350 A - 3 poles 3d
- Код товара: EZC400H3350N
- Артикул: EZC400H3350N
- Штрихкод:
- Наличие: В наличии