| range of product |
Easypact CVS100...250
| |
| product or component type |
Earth leakage circuit breaker
| |
| device short name |
Vigi CVS100B
| |
| device application |
Distribution
| |
| poles description |
3P
| |
| protected poles description |
3d
| |
| earth-leakage protection |
With
| |
| [In] rated current |
100 A ( 40 °C )
| |
| breaking capacity code |
B
| |
| network type |
AC
| |
| [Ue] rated operational voltage |
440 V AC conforming to EN/IEC 60947-2 50/60 Hz
| |
| breaking capacity |
40 kA Icu conforming to IEC 60947-2 at 220/240 V AC 50/60 Hz
| |
| utilisation category |
Category A
| |
| trip unit name |
TM-D
| |
| trip unit technology |
Thermal-magnetic
| |
| trip unit rating |
80 A ( 40 °C )
| |
| protection type |
Short-circuit protection (magnetic)
Overload protection (thermal) | |
| earth-leakage add-on module name |
MH
|
| network frequency |
50/60 Hz
| |
| control type |
Toggle
| |
| mounting mode |
Fixed
| |
| mounting support |
Backplate
| |
| upside connection |
Front
| |
| downside connection |
Front
| |
| [Ui] rated insulation voltage |
690 V conforming to EN/IEC 60947-2
| |
| [Uimp] rated impulse withstand voltage |
8 kV conforming to EN/IEC 60947-2
| |
| [Ics] rated service breaking capacity |
15 kA conforming to IEC 60947-2 440 V AC 50/60 Hz
| |
| mechanical durability |
30000 cycles
| |
| electrical durability |
12000 cycles conforming to IEC 60947-2 415 V In
| |
| connection pitch |
35 mm
| |
| contact position indicator |
Yes
| |
| long time pick-up adjustment type Ir |
Adjustable
| |
| long time pick-up adjustment range |
0.7...1 x In
| |
| long time delay adjustment type |
Fixed
| |
| short-time delay adjustment type |
Fixed
| |
| instantaneous pick-up adjustment type Ii |
Fixed
| |
| instantaneous pick-up adjustment range |
640 A
| |
| earth-leakage protection class |
Class A
| |
| residual earth-leakage sensitity adjustment type |
Adjustable 5 settings
| |
| [IΔn] residual earth-leakage sensitive adjustment |
3 A
0.03 A 1 A 0.3 A 10 A | |
| residual earth-leakage time delay adjustment type |
Adjustable 5 settings
| |
| [Δt] residual earth-leakage time delay adjustment |
0 ms < 40 ms
| |
| height |
236 mm
| |
| width |
105 mm
| |
| depth |
86 mm
|
| electrical shock protection class |
Class II
| |
| standards |
EN 60947-2
IEC 60947-2 | |
| product certifications |
GOST
IEC | |
| pollution degree |
3 conforming to IEC 60947-1
| |
| ambient air temperature for operation |
-25...70 °C
| |
| ambient air temperature for storage |
-50...85 °C
|
| Sustainable offer status |
Green Premium product
| |
| RoHS (date code: YYWW) |
Compliant - since 1041 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity
| |
| REACh | ||
| Product environmental profile |
AvailableProduct environmental
| |
| Product end of life instructions |
AvailableEnd of life manual
|
| Warranty period |
18 months
|
Easypact CVS - CVS100B Vigi MH TM80D circuit breaker - 3P/3d
- Код товара: LV510366
- Артикул: LV510366
- Штрихкод:
- Наличие: В наличии